Air separators

Applications

Designed for removing air from water.

Used in heating systems at the highest temperature point (downstream of the boiler or heat exchanger). Air separators reduce system corrosion, extend pump life by reducing cavitation, flow noise and system noise.

Features

– automatic removal of air from heating water

– installed on horizontal lines

Air separator
Air separator

Design

Low-carbon steel cylindrical tanks with external paint coat finish (acid-resistant steel version available). Inlet (2) and outlet (3) ports in the shell (1) for circulation pump. Special ring (4) insert for removing air from water. Automatic air relief valve (5) in the top section. Cleaning via drain valve port (6) in the bottom sectio

air separator
Air separator SEP (design and dimensions)

Principle of operation

Heating medium is discharged via port (2) to the tank. The flow rate is reduced inside the tank. The air bubbles and micro-air bubbles settle on the ring (4) walls. The air is removed to the top tank section and discharged via the automatic air relief valve (5). Air-free heating medium is discharged via port (3).

Technical specifications

Technical specifications

Type DN Capacitydm3 Rated temperatureoC

Rated pressure

bar

Net weight

kg

Dimensions
D L H1 H
SEP 15 15 1.1 110/150 6/10/16 3 108 265 105 210
SEP 20 20 1.1 3.5 108 265 105 210
SEP 25 25 1.1 3.8 108 265 105 210
SEP 32 32 1.1 4.4 108 265 105 210
SEP 40 40 4.6 11 159 295 120 305
SEP 50 50 4.6 12 159 295 120 305
SEP 65 65 4.6 13 159 295 120 305
SEP 80 80 30 27 273 450 195 600
SEP 100 100 30 30 273 450 195 600
SEP 125 125 47 52 324 500 300 780
SEP 150 150 47 55 324 500 300 780
SEP 200 200 130 80 457 667 410 980
SEP 250-500 special version for DN250 to DN500 diameter

– PN16 flanges

– flange dimensions as per PN-EN 1092-1

mark as per relevant regulations (depending on T, p, V).

© 2024 Copyright Termen